Fiber Optic Trunk
304&/#&3(&3
)%$4
®
$"#-*/(4:45&.
Inter-building backbone cabling
telecom closet
Fiber optic cabling in data centers
Number of Fibers 4 8 12 16 24 48 72
Length of Legs [cm] 85-100 65-100 45-100 54.5-84 38.5-84 50 –65 45 –70
Diameter Installation Tube [mm] 28 28 28 35 35 60 60
Max. Tensile Force Installation Tube [N] 500 600
Max. Tensile Force Cable [N] 1200 1200 1200 1200 1200 3000 3000
Min. Bending Radius (Installation) [mm] 160 160 160 164 164 240 250
Min. Bending Radius (Operation) [mm] 120 120 120 128 128 180 188
Crush Resistance Installation Tube [N/cm] 100
Crush Resistance Cable [N/cm] 150 150 150 150 150 200 200
Diameter Cable Drum [mm] 800
Temperature Range (Installation) [ºC] 0 to +50
Temperature Range (Operation) [ºC] -20 to +60
P
RE
CONNECT
®
Cable with loose tube construction, outer sheath
made of FR-LSZH material, non-metallic strain
relief elements
Optionally with rodent protection
Longitudinally and transversely waterproof due to
Flame retardant acc. to IEC 60332-1 and IEC
60332-3 C
No corrosive gas emission acc. to IEC 60754-2
Low smoke emission acc. to IEC 61034-2
Installation tube acc. to IP50, dust protected,
crush resistant
Rosenberger’s P
RE
CONNECT
®
cables for outdoor
application are ordered using four digits:Digit1,
Sheath type selection;Digit2,Fiber type selection;
P
RE
CONNECT
®
Cables for Outdoor
Application
X X X
20
3: LSZH
6: OFNR
8: OFNP
1: SM, 9/125µm 1: SC/SC 1: 4
2: MM, 50/125µm 2: ST/ST 2: 6
3: MM, G62.5/125µm 3: SC/ST 3: 8
5: OM3 4: FC/FC 4: 12
6: OM4 5: SC-DC/SC-DC 5: 16
6: MTRJ/MTRJ 6: 24
7: LC/LC 7: 36
8: FC/ST 8: 48
9: FC/FC-APC 9: 72
A: LC/SC A: 144
B: FC/SC
C: FC-APC/FC-APC
F: MTP/MTP
M: MTP/LC
20X X X X
Digit3,Connector type selection;Digit4,Number
below.
Comentários a estes Manuais